A-60 vs B-15: marine fire classes explained

A-60 and B-15 are fire classes for ship divisions defined in SOLAS Chapter II-2 and tested under the IMO FTP Code. An A-60 division is steel-based and must stop smoke and flame for 60 minutes while keeping the unexposed side cool for 60 minutes. A B-15 division must stop flame for 30 minutes and keep the unexposed side cool for 15 minutes. A-class is used around stairways, machinery and control spaces; B-class is used for cabin and corridor partitions.

The fire classes side by side

ClassIntegrity (stops smoke and flame)Insulation timeConstruction
A-6060 minutes60 minutesSteel or equivalent, insulated
A-30 / A-1560 minutes30 / 15 minutesSteel or equivalent, insulated
A-060 minutesNoneSteel or equivalent
B-1530 minutes15 minutesApproved non-combustible materials, e.g. mineral wool panels
B-030 minutesNoneApproved non-combustible materials

Insulation means the average temperature rise on the unexposed side stays below 140 °C and no single point rises more than 180 °C during the stated time.

Where each class is used

  • A-60: boundaries of machinery spaces, stairway enclosures, control stations, galleys (as SOLAS tables require)
  • A-0: steel divisions where integrity is needed without insulation
  • B-15: cabin-to-corridor bulkheads and many accommodation partitions
  • B-0: cabin-to-cabin partitions and linings where the tables allow

What this means when you order

  • Order doors in the same class as the division they sit in
  • Check that the door model is certified for that bulkhead type
  • For EU-flagged ships, require the MED wheelmark; for others, the class type approval the vessel needs
  • Ask for certificate numbers in the quotation and verify them

B-15 / B-0 panels · A-60 and B-15 doors · How certificates work

Frequently asked questions

Is A-60 better than B-15?

A-60 is a higher fire class: it applies to steel divisions and must resist fire for 60 minutes with 60 minutes of insulation. B-15 divisions resist fire for 30 minutes with 15 minutes of insulation. The class required for each bulkhead or door is set by SOLAS Chapter II-2 tables, not by choice.

Can a B-15 panel be used where A-60 is required?

No. A-class divisions must be steel or equivalent and pass the A-class test. A B-class panel system cannot replace an A-class division.

Which test standard applies?

Both are tested to the IMO 2010 Fire Test Procedures Code (FTP Code), Part 3, with the standard fire curve.